Fuseology - Fuse Troubleshooting
Overcurrent devices provide two main purposes in an electrical circuit:
1. To protect components, equipment and associated wiring from costly
damage.
2. To isolate sub-systems from the main system once a current fault has
occurred.
Fuses and circuit breakers are commonly selected as the preferred
overcurrent devices.
Fuses
Fuses are current sensitive devices and selected to be the weakest link in
the circuit. Circuit protection is provided when the fuse link melts and safely
interrupts the overcurrent demand. The key criteria to judge the
performance of a fuse is the time versus current characteristic curve.
This curve can be used to match the fuse with the anticipated overcurrent
load expected in the application.
Thermal Circuit Breakers
The basic components of a thermal circuit breaker are the composite alloy
reed, two precious metal contacts and the interconnecting terminals. When
an overcurrent occurs, heat is generated as the current flows through the
reed causing the reed to deflect and snap open. This separates the contacts
and safely interrupts the current flow. Two important parameters used to
judge the performance of thermal circuit breakers are the time versus
current characteristic curve, similar to the fuse, along with the speed at
which the contacts snap open. The relative speed at which, the contacts
separate is a measure of the cycle life under electrical loading demands.
Cooper Bussmann carefully designs its snap acting reed element to ensure
long cycle performance for its products.
Types of Overcurrent
Short-Circuit: Short-circuit is a current condition that greatly exceeds the
rating of the device. It is caused when a malfunction or accident creates a
break in the normal path allowing electricity to flow directly to ground. This
shorter current path bypasses the resistance offered by the circuit
components connected in the normal current path. In this situation, there is
virtually no resistance to impede the current and the current will build to a
level where the heat generated can cause insulation and/or equipment
breakdown.
Overload: An overload is an overcurrent that is within the normal current
path. Overloads occur when the current exceeds the value for which the
equipment or associated wiring is rated. This typically occurs when too
many devices are connected to the circuit or when a device connected to
the circuit malfunctions. Sustained overloads may slowly cause overheating
of the wiring and the components. The circuit protection device must open
before these types of overloads cause damage.
Selecting Overcurrent Protection
During normal conditions, an overcurrent protection device must carry the
current without nuisance openings. However, when an overload or short-
circuit occurs, the device must interrupt the overcurrent and withstand the
voltage across the device after arcing. To properly select an overcurrent
device, the following items must be carefully considered:
Voltage Rating: Represents the maximum system voltage present in
the circuit in which the overcurrent device is installed. The system
voltage should not exceed this value for proper operation of the device
during an overcurrent event.
Current Rating: This is the amp value marked on the circuit protection
device. The circuit protection device is designed to handle this value
under steady operating conditions and at ambient temperatures near
25°C. The current rating of the fuse should not exceed the rating of the
device.
Characteristics of Equipment to be Protected/In-rush Characteristics:
During the operation of protected equipment, system current can
significantly vary. This is particularly evident when motor or other inductive
loads in the circuit cause large current surges during start-up or shutdown.
A time-delay fuse should be used in applications where in-rush currents are
possible.
Troubleshooting Technique
Important: Before replacing any fuse or circuit breaker, always turn off
power, and determine and remedy the cause of the fuse or circuit breaker
opening.
? Always replace an open fuse with one of the same type having the correct
voltage and amp rating for the application or called for by the equipment
manufacturer.
? Always replace a non-working circuit breaker with one of the same type
having the correct voltage and amp rating for the application or called for
by the equipment manufacturer. If replacing a fuse with a circuit breaker,
consult your owner’s manual for recommendations.
Because fuses contain no moving parts, they do not generally operate due
to wear-and-tear. When a fuse opens, it's important that you determine and
correct what caused the overcurrent situation in the first place. Otherwise,
the replacement fuse is likely to open, too - and the circuit will still not
function as intended.
Automotive: Fuses are installed in one or more fuse blocks - which can be
located in various locations in the vehicle, depending on its make and
model. Typically, fuse panels can be found in the passenger compartment,
below the steering wheel; in the engine compartment; or in some cases, in
the trunk. See the vehicle owner's manual for the precise location of the
fuse block(s).
On most vehicles, each clip in the fuse block will be labeled, to help you
identify which circuit the fuse protects (wipers, radio, dome light, etc.). The
fuse itself is labeled with an amp rating, and (in the case of blade fuses) a
color coding.
Home: For circuits carrying 120/240 volts, please refer troubleshooting and
servicing to a qualified electrician.
46
For product information and Data Sheets, visit www.cooperbussmann.com
相关PDF资料
BK/FLF-60 FUSE 60A AUTO
BK/GMA-V-250-R FUSE 250MA 250V FAST GLASS AXIAL
BK/HHB-R408 FUSEHOLDER INLINE 1/4X7/8-1.25"
BK/HLD-HH FUSEHOLDER 1/4" 15A PIN IND QC
BK/HPD FUSEHOLDER 13/32" 30A PANEL MNT
BK/KTK-15 FUSE 15A 600V FAST UL CSA
BK/MDL-3/8-R FUSE 3/8A 250V T-LAG GLS MDL
BK/MDQ-4 FUSE 4A 250V T-LAG MDQ
相关代理商/技术参数
BK/CB184F-120 功能描述:断路器 AUTO CIRCT BREAKERS RoHS:否 制造商:Phoenix Contact 产品:Device Circuit Breakers 产品类型:Thermomagnetic 电流额定值:2 A 电压额定值 AC:240 V, 277 V 电压额定值 DC:50 V 极数:1 Pole 执行器类型:Slide 电路功能:Trip Free 系列:CB TM1 工作温度范围:- 30 C to + 60 C 照明:No
BK/CB184F-150 功能描述:断路器 AUTO CIRCT BREAKERS RoHS:否 制造商:Phoenix Contact 产品:Device Circuit Breakers 产品类型:Thermomagnetic 电流额定值:2 A 电压额定值 AC:240 V, 277 V 电压额定值 DC:50 V 极数:1 Pole 执行器类型:Slide 电路功能:Trip Free 系列:CB TM1 工作温度范围:- 30 C to + 60 C 照明:No
BK/CB185-100 功能描述:断路器 AUTO CIRCUIT BREAKER RoHS:否 制造商:Phoenix Contact 产品:Device Circuit Breakers 产品类型:Thermomagnetic 电流额定值:2 A 电压额定值 AC:240 V, 277 V 电压额定值 DC:50 V 极数:1 Pole 执行器类型:Slide 电路功能:Trip Free 系列:CB TM1 工作温度范围:- 30 C to + 60 C 照明:No
BK/CB185-120 制造商:Cooper Bussmann 功能描述:AUTO CIRCUIT BREAKER - Bulk 制造商:COOPER BUSSMANN 功能描述:AUTO CIRCUIT BREAKER
BK/CB185-135 制造商:Cooper Bussmann 功能描述:AUTO CIRCUIT BREAKER - Bulk 制造商:COOPER BUSSMANN 功能描述:AUTO CIRCUIT BREAKER
BK/CB185-150 功能描述:断路器 AUTO CIRCUIT BREAKER RoHS:否 制造商:Phoenix Contact 产品:Device Circuit Breakers 产品类型:Thermomagnetic 电流额定值:2 A 电压额定值 AC:240 V, 277 V 电压额定值 DC:50 V 极数:1 Pole 执行器类型:Slide 电路功能:Trip Free 系列:CB TM1 工作温度范围:- 30 C to + 60 C 照明:No
BK/CB185-50 功能描述:断路器 AUTO CIRCUIT BREAKER RoHS:否 制造商:Phoenix Contact 产品:Device Circuit Breakers 产品类型:Thermomagnetic 电流额定值:2 A 电压额定值 AC:240 V, 277 V 电压额定值 DC:50 V 极数:1 Pole 执行器类型:Slide 电路功能:Trip Free 系列:CB TM1 工作温度范围:- 30 C to + 60 C 照明:No
BK/CB185-60 制造商:COOPER BUSSMANN 功能描述:AUTO CIRCUIT BREAKER